Media: | Air |
---|---|
Temperature: | Ordinary Temperature |
Actuator: | Pneumatic |
Connection Form: | Clamp |
Type: | Direct Acting |
Material: | Carbon Steel |
Customization: |
---|
Suppliers with verified business licenses
Specification:
Voltage (up to)
|
kV
|
24
|
---|---|---|
Frequency
|
Hz
|
50/60
|
Power-frequency withstand voltage/across isolating distance
|
kV
|
up to 60/70
|
Lightning impulse withstand voltage/across isolating distance
|
kV
|
up to 125/145
|
Normal current at 40oC ambient temperatures (up tp)
- at 50 Hz - at 60 Hz |
A
|
15,000 14,250 |
Short-time withstand current/duration (up to)
- Generator circuit - Earthing circuits |
kA/s
|
110/3 110/1 |
Peak withstand current
|
kA
|
302
|
Short-circuit breaking current (up to)
|
kA
|
110
|
Short-circuit making current
|
kA
|
302
|
Suppliers with verified business licenses